ControlForge Timers, Counters & Function Blocks Guide
James M. Belcher Founder, JMB Technical Services LLC April 2026 | ControlForge v1.0.535
1. Overview
ControlForge implements 14 IEC 61131-3 standard function blocks. Unlike plain functions, function blocks retain state between scan cycles — a timer remembers how long it has been running, a counter remembers its count, a PID controller remembers its integral term.
| Category | Function Blocks | Description |
|---|---|---|
| Timers | TON, TOF, TP, RTO | Time-based delays, pulses, and accumulation |
| Counters | CTU, CTD, CTUD | Event counting (up, down, bidirectional) |
| Bistables | SR, RS | Set/reset latches with priority control |
| Edge Triggers | R_TRIG, F_TRIG | Rising and falling edge detection |
| PID Controllers | PID, PIDE | Proportional-Integral-Derivative feedback control |
How Function Blocks Work in ST
Function blocks are declared as variables, then called with named parameters:
PROGRAM POU_Example
VAR
myTimer : TON; (* Declare instance *)
startButton : BOOL;
output : BOOL;
END_VAR
myTimer(IN := startButton, PT := T#5s); (* Call with inputs *)
output := myTimer.Q; (* Read outputs *)
END_PROGRAM
Each instance maintains its own state. You can have multiple instances of the same type:
VAR
pumpDelay : TON;
fanDelay : TON;
alarmDelay : TON;
END_VAR
2. Timers
2.1 TON — Timer On-Delay
Output Q goes TRUE after IN has been TRUE continuously for PT duration. If IN goes FALSE before PT expires, the timer resets.
VAR
startDelay : TON;
END_VAR
startDelay(IN := startButton, PT := T#3s);
IF startDelay.Q THEN
(* Button held for 3 seconds — start motor *)
motor := TRUE;
END_IF;
Inputs:
| Parameter | Type | Description |
|---|---|---|
IN | BOOL | Enable input — timer runs while TRUE |
PT | TIME | Preset time (e.g., T#3s, T#500ms, T#1h30m) |
R | BOOL | Reset — clears elapsed time and output |
Outputs:
| Parameter | Type | Description |
|---|---|---|
Q | BOOL | Output — TRUE when elapsed >= PT |
ET | TIME | Elapsed time (capped at PT) |
DN | BOOL | Done — TRUE when timing complete |
TT | BOOL | Timer Timing — TRUE while actively counting |
EN | BOOL | Enabled — mirrors IN |
Timing Diagram:
IN: ──┐ ┌──────────────────────┐ ┌───
└─────┘ └─────┘
PT: ======== (3 seconds)
Q: ─────────────────┐ ┌─────────
└─────────────┘
<--- 3s --->
IN went FALSE Q stays FALSE
before PT, until IN has been
timer reset TRUE for full PT
2.2 TOF — Timer Off-Delay
Output Q goes TRUE immediately when IN goes TRUE. When IN goes FALSE, Q stays TRUE for PT duration before going FALSE.
VAR
coolDown : TOF;
END_VAR
coolDown(IN := runCommand, PT := T#10s);
(* Fan keeps running 10 seconds after run command stops *)
fan := coolDown.Q;
Inputs:
| Parameter | Type | Description |
|---|---|---|
IN | BOOL | Enable input |
PT | TIME | Off-delay duration |
R | BOOL | Reset |
Outputs: Same as TON (Q, ET, DN, TT, EN).
Timing Diagram:
IN: ──┐ ┌────────────┐ ┌───
└─────┘ └─────┘
Q: ──┐ ┌────────────┐ ┌───
└─────┘ └───────────┘
<-- 10s -->
Q holds TRUE
after IN falls
2.3 TP — Timer Pulse
Generates a fixed-width pulse on the rising edge of IN. Not retriggerable — if IN pulses again during an active pulse, it is ignored.
VAR
oneShot : TP;
END_VAR
oneShot(IN := trigger, PT := T#200ms);
(* 200ms pulse on every rising edge of trigger *)
solenoid := oneShot.Q;
Inputs:
| Parameter | Type | Description |
|---|---|---|
IN | BOOL | Trigger input (rising edge starts pulse) |
PT | TIME | Pulse width |
Outputs: Same as TON (Q, ET, DN, TT, EN).
Timing Diagram:
IN: ──┐ ┌──┐ ┌──┐
└─┘ └─────┘ └───
^ignored (pulse active)
Q: ──┐ ┌──────────┐
└────────────────┘ └───
<---- 200ms ----> <-200ms->
2.4 RTO — Retentive Timer On-Delay
Accumulates time while IN is TRUE. Unlike TON, it does not reset when IN goes FALSE — accumulated time is retained. Only an explicit R (reset) input clears the timer.
VAR
runHours : RTO;
totalRuntime : TIME;
END_VAR
runHours(IN := motorRunning, PT := T#8h, R := resetBtn);
totalRuntime := runHours.ET;
IF runHours.Q THEN
(* Motor has accumulated 8 hours of runtime — schedule maintenance *)
maintenanceDue := TRUE;
END_IF;
Inputs:
| Parameter | Type | Description |
|---|---|---|
IN | BOOL | Enable — accumulates time while TRUE |
PT | TIME | Preset time (total accumulation target) |
R | BOOL | Reset — clears accumulated time and output |
Outputs: Same as TON (Q, ET, DN, TT, EN).
Timing Diagram:
IN: ──┐ ┌──┐ ┌──────────────
└─────┘ └─────┘
ET: 0 2s 2s 4s 4s 6s 8s...
^retained ^retained
when IN when IN
goes FALSE goes FALSE
Q: ──────────────────────────┐
└── (Q stays TRUE until R)
ET >= PT
3. Counters
3.1 CTU — Count Up
Increments CV on each rising edge of CU. Q becomes TRUE when CV reaches PV.
VAR
partCount : CTU;
END_VAR
partCount(CU := proxSensor, PV := 100, R := resetBtn);
IF partCount.Q THEN
(* 100 parts counted — signal batch complete *)
batchDone := TRUE;
END_IF;
currentCount := partCount.CV;
Inputs:
| Parameter | Type | Description |
|---|---|---|
CU | BOOL | Count Up — rising edge increments CV |
PV | INT | Preset value (target count) |
R | BOOL | Reset — sets CV to 0 |
LD | BOOL | Load — loads PV into CV |
Outputs:
| Parameter | Type | Description |
|---|---|---|
Q | BOOL | Output — TRUE when CV >= PV |
CV | INT | Current count value |
3.2 CTD — Count Down
Decrements CV on each rising edge of CD. Q becomes TRUE when CV reaches 0.
VAR
remaining : CTD;
END_VAR
remaining(CD := dispenseSensor, PV := 50, LD := loadBtn);
IF remaining.Q THEN
(* All items dispensed *)
hopperEmpty := TRUE;
END_IF;
itemsLeft := remaining.CV;
Inputs:
| Parameter | Type | Description |
|---|---|---|
CD | BOOL | Count Down — rising edge decrements CV |
PV | INT | Preset value (loaded by LD) |
R | BOOL | Reset — sets CV to 0 |
LD | BOOL | Load — loads PV into CV |
Outputs:
| Parameter | Type | Description |
|---|---|---|
Q | BOOL | Output — TRUE when CV <= 0 |
CV | INT | Current count value |
3.3 CTUD — Count Up/Down
Bidirectional counter with separate up and down inputs.
VAR
position : CTUD;
END_VAR
position(CU := forwardPulse, CD := reversePulse, PV := 1000, R := homeBtn);
atUpperLimit := position.QU; (* CV >= 1000 *)
atLowerLimit := position.QD; (* CV <= 0 *)
currentPos := position.CV;
Inputs:
| Parameter | Type | Description |
|---|---|---|
CU | BOOL | Count Up — rising edge increments CV |
CD | BOOL | Count Down — rising edge decrements CV |
PV | INT | Preset value (upper threshold) |
R | BOOL | Reset — sets CV to 0 |
LD | BOOL | Load — loads PV into CV |
Outputs:
| Parameter | Type | Description |
|---|---|---|
QU | BOOL | Upper limit — TRUE when CV >= PV |
QD | BOOL | Lower limit — TRUE when CV <= 0 |
CV | INT | Current count value |
4. Bistables (Latches)
4.1 SR — Set-Reset (Set Dominant)
When both S1 and R are TRUE, Set wins — Q1 stays TRUE.
VAR
latch : SR;
END_VAR
latch(S1 := startBtn, R := stopBtn);
motorEnabled := latch.Q1;
| Input | Type | Description |
|---|---|---|
S1 | BOOL | Set (dominant) |
R | BOOL | Reset |
| Output | Type | Description |
|---|---|---|
Q1 | BOOL | Latched output (retained) |
Logic: Q1 := S1 OR (NOT R AND Q1)
4.2 RS — Reset-Set (Reset Dominant)
When both S and R1 are TRUE, Reset wins — Q1 goes FALSE. Safer for emergency stop circuits.
VAR
safeLatch : RS;
END_VAR
safeLatch(S := runPermit, R1 := eStop);
motorAllowed := safeLatch.Q1;
| Input | Type | Description |
|---|---|---|
S | BOOL | Set |
R1 | BOOL | Reset (dominant) |
| Output | Type | Description |
|---|---|---|
Q1 | BOOL | Latched output (retained) |
Logic: Q1 := NOT R1 AND (S OR Q1)
Safety: Use RS (reset-dominant) for safety-critical latches. An E-stop should always be able to override a run command, even if both signals are active simultaneously.
5. Edge Triggers
5.1 R_TRIG — Rising Edge Detector
Output Q is TRUE for exactly one scan when CLK transitions from FALSE to TRUE.
VAR
riseDetect : R_TRIG;
END_VAR
riseDetect(CLK := inputSignal);
IF riseDetect.Q THEN
(* Rising edge detected — execute once *)
batchCount := batchCount + 1;
END_IF;
| Input | Type | Description |
|---|---|---|
CLK | BOOL | Signal to monitor |
| Output | Type | Description |
|---|---|---|
Q | BOOL | TRUE for one scan on rising edge |
5.2 F_TRIG — Falling Edge Detector
Output Q is TRUE for exactly one scan when CLK transitions from TRUE to FALSE.
VAR
fallDetect : F_TRIG;
END_VAR
fallDetect(CLK := inputSignal);
IF fallDetect.Q THEN
(* Falling edge detected — signal just went off *)
offCount := offCount + 1;
END_IF;
| Input | Type | Description |
|---|---|---|
CLK | BOOL | Signal to monitor |
| Output | Type | Description |
|---|---|---|
Q | BOOL | TRUE for one scan on falling edge |
6. PID Controllers
6.1 PID — Standard PID Controller
Proportional-Integral-Derivative feedback controller with anti-windup.
VAR
tempPID : PID;
heaterOutput : REAL;
END_VAR
tempPID(
EN := TRUE,
PV := actualTemp, (* Measured temperature *)
SP := setpointTemp, (* Desired temperature *)
KP := 10.0, (* Proportional gain *)
KI := 0.5, (* Integral gain *)
KD := 2.0, (* Derivative gain *)
CYCLE := 0.1, (* Scan time in seconds *)
MN := 0.0, (* Min output *)
MX := 100.0 (* Max output *)
);
heaterOutput := tempPID.CV;
Inputs:
| Parameter | Type | Default | Description |
|---|---|---|---|
EN | BOOL | TRUE | Enable |
PV | REAL | required | Process variable (measurement) |
SP | REAL | required | Setpoint (target) |
KP | REAL | 1.0 | Proportional gain |
KI | REAL | 0.0 | Integral gain |
KD | REAL | 0.0 | Derivative gain |
CYCLE | REAL | 0.1 | Scan time in seconds |
MN | REAL | 0.0 | Minimum output |
MX | REAL | 100.0 | Maximum output |
MR | BOOL | FALSE | Manual reset (clears integral) |
Outputs:
| Parameter | Type | Description |
|---|---|---|
CV | REAL | Control variable (calculated output) |
E | REAL | Error (SP - PV) |
ERR | BOOL | TRUE when this call held its output (see Faults) |
STATUS | DINT | 0 OK, 1 an input or the result was NaN/±Inf, 2 MN > MX, 3 CYCLE ≤ 0 |
Algorithm:
Error = SP - PV
P = KP * Error
I = KI * accumulated_integral
D = KD * (Error - prevError) / CYCLE
CV = CLAMP(P + I + D, MN, MX)
No windup, in either direction. When the output is at MN or MX and the integral's next step would push it further, the integral does not move that scan. This is judged on the output, so a reverse-acting loop (negative gains) is protected exactly like a forward one.
Faults: the output holds, never NaN. If an input is NaN or ±Inf (a failed
sensor, a bad protocol value), or MN > MX, or CYCLE ≤ 0, the call holds CV
and E at their last good values, does not move the integral, and sets ERR
with the reason in STATUS. The first good call after that carries on from
where it held, with no derivative kick. Validation warns before Download when
both limits are literals that cross, or CYCLE is a literal ≤ 0.
loopPID(PV := flowMeter, SP := 120.0, KP := 0.8, KI := 0.3, CYCLE := 0.1, MN := 0.0, MX := 100.0);
valve := loopPID.CV;
IF loopPID.ERR THEN
alarmFlowLoop := TRUE; (* holding: STATUS says why *)
END_IF;
6.2 PIDE — Enhanced PID (Rockwell-Style)
Extended PID with feed-forward, output bias, manual mode, setpoint limits, and alarm thresholds.
VAR
reactorPID : PIDE;
END_VAR
reactorPID(
EN := TRUE,
PV := reactorTemp,
SP := 180.0,
KP := 5.0,
KI := 0.2,
KD := 1.0,
CYCLE := 0.1,
FF := steamFlow * 0.5, (* Feed-forward from steam *)
BIAS := 10.0, (* Output offset *)
MAXO := 100.0, (* Max output *)
MINO := 0.0, (* Min output *)
MAXS := 200.0, (* Max setpoint *)
MINS := 50.0 (* Min setpoint *)
);
valveOutput := reactorPID.CV;
spClamped := reactorPID.SPH OR reactorPID.SPL;
Additional Inputs (beyond PID):
| Parameter | Type | Default | Description |
|---|---|---|---|
FF | REAL | 0.0 | Feed-forward term (added directly to output) |
BIAS | REAL | 0.0 | Output bias/offset |
MAXO | REAL | 100.0 | Maximum output |
MINO | REAL | 0.0 | Minimum output |
MAXS | REAL | 100.0 | Maximum setpoint limit |
MINS | REAL | 0.0 | Minimum setpoint limit |
MAXI | REAL | 100.0 | Maximum integral accumulation |
MINI | REAL | -100.0 | Minimum integral accumulation |
DPTS | BOOL | FALSE | Dependent gains mode |
MO | BOOL | FALSE | Manual output mode (CV = MOCV) |
MOCV | REAL | 0.0 | Manual CV value |
INIMAN | BOOL | FALSE | Initialize integral from MOCV |
Additional Outputs:
| Parameter | Type | Description |
|---|---|---|
SPH | BOOL | Setpoint clamped to MAXS |
SPL | BOOL | Setpoint clamped to MINS |
ERR | BOOL | TRUE when this call held its output (as for PID; see PID Faults) |
STATUS | DINT | 0 OK, 1 non-finite input or result, 2 crossed limits (output, integral or setpoint), 3 CYCLE ≤ 0 |
PIDE follows PID's fault rule: a NaN/±Inf input (MOCV included in manual
mode), crossed limits or CYCLE ≤ 0 hold CV and set ERR. Dependent gains
(DPTS) compute KP·(E + KI·I) + D, so KP = 0 is safe.
Key Differences from PID:
- Derivative is calculated on PV (not error) to avoid derivative kick on setpoint changes
- Feed-forward term for measurable disturbance rejection
- Setpoint clamping with limit flags
- Manual mode for bumpless transfer between auto and manual
- Bounded integral accumulation (separate from output limits)
7. TIME Literals
All timer presets use IEC 61131-3 TIME literals:
| Literal | Duration |
|---|---|
T#500ms | 500 milliseconds |
T#1s | 1 second |
T#5s | 5 seconds |
T#1m30s | 1 minute 30 seconds |
T#1h | 1 hour |
T#1h30m | 1 hour 30 minutes |
T#2d | 2 days |
T#100ms | 100 milliseconds |
T#10us | 10 microseconds |
8. Complete Example: Pump Station
A realistic pump control program using timers, counters, edge triggers, and PID.
PROGRAM POU_PumpStation
VAR
(* Inputs *)
startBtn : BOOL;
stopBtn : BOOL;
eStop : BOOL;
levelSensor : REAL; (* 0-100% *)
flowSensor : REAL; (* GPM *)
(* Function block instances *)
runLatch : RS; (* Reset-dominant for safety *)
startDelay : TON; (* Anti-short-cycle delay *)
runTimer : RTO; (* Accumulate total run hours *)
cycleCount : CTU; (* Count start/stop cycles *)
startEdge : R_TRIG; (* Detect start events *)
levelPID : PID; (* Level control *)
dryRunTimer : TON; (* Dry run protection *)
(* Outputs *)
pumpRun : BOOL;
vfdSpeed : REAL;
maintenanceDue : BOOL;
dryRunFault : BOOL;
END_VAR
(* Safety latch — E-stop always wins *)
runLatch(S := startBtn AND NOT dryRunFault, R1 := stopBtn OR eStop);
(* Anti-short-cycle: must wait 30s between starts *)
startDelay(IN := NOT runLatch.Q1, PT := T#30s);
pumpRun := runLatch.Q1 AND startDelay.Q;
(* Count start events *)
startEdge(CLK := pumpRun);
cycleCount(CU := startEdge.Q, PV := 10000, R := FALSE);
(* Accumulate runtime for maintenance scheduling *)
runTimer(IN := pumpRun, PT := T#2000h, R := FALSE);
maintenanceDue := runTimer.Q;
(* Level PID — controls VFD speed *)
levelPID(
EN := pumpRun,
PV := levelSensor,
SP := 75.0, (* Maintain 75% level *)
KP := 5.0,
KI := 0.3,
KD := 0.5,
CYCLE := 0.05, (* 50ms scan *)
MN := 20.0, (* Min speed 20% *)
MX := 100.0 (* Max speed 100% *)
);
vfdSpeed := levelPID.CV;
(* Dry run protection: fault if running with no flow for 10s *)
dryRunTimer(IN := pumpRun AND (flowSensor < 1.0), PT := T#10s);
IF dryRunTimer.Q THEN
dryRunFault := TRUE; (* Latches until operator clears *)
END_IF;
END_PROGRAM
Appendix A: Quick Reference
Timers
| FB | Purpose | Key I/O |
|---|---|---|
| TON | On-delay | IN + PT → Q after delay |
| TOF | Off-delay | Q holds TRUE for PT after IN falls |
| TP | Pulse | Fixed-width pulse on rising edge |
| RTO | Retentive on-delay | Accumulates time, retains on IN=FALSE, needs R to clear |
Counters
| FB | Purpose | Key I/O |
|---|---|---|
| CTU | Count up | CU rising edge → CV++, Q when CV >= PV |
| CTD | Count down | CD rising edge → CV--, Q when CV <= 0 |
| CTUD | Up/down | CU/CD edges, QU (upper), QD (lower) |
Bistables
| FB | Purpose | Priority |
|---|---|---|
| SR | Set-Reset latch | Set dominant |
| RS | Reset-Set latch | Reset dominant (use for safety) |
Edge Triggers
| FB | Purpose | Output |
|---|---|---|
| R_TRIG | Rising edge | Q = TRUE for one scan on FALSE→TRUE |
| F_TRIG | Falling edge | Q = TRUE for one scan on TRUE→FALSE |
PID
| FB | Purpose | Key Features |
|---|---|---|
| PID | Standard PID | KP/KI/KD, anti-windup, output clamping |
| PIDE | Enhanced PID | Feed-forward, bias, manual mode, SP limits, alarms |
ControlForge v1.0.535 | IEC 61131-3 Function Blocks | Timers, Counters, PID
© 2026 JMB Technical Services LLC. All rights reserved. Back to All Guides